    Overview
     

     Overview

     
    • Designed for building automation applications
    • ±3 %RH accuracy
    • Full 0 ... 100 %RH measurement range
    • -20 ... +60 °C (-4 ... +140 °F) operating range
    • IP65 (NEMA 4) metal housing
    • Excellent stability and high reliability
    • Fully interchangeable Vaisala INTERCAP® Sensor
    • Variety of analog signal outputs available
    Technical Specifications
     

     Technical Specifications

     

    Relative Humidity

    Measurement range
    0 ... 100 %RH
    Typical accuracy
    ​   Temperature range 0 ... +40 °C (+32 ... +104 °F)
    ​      0 ... 90 %RH ±3 %RH
    ​      90 ... 100 %RH ±5 %RH
    ​   Temperature range -20 ... 0 °C, +40 ... +60 °C
    (-4 ... +32 °F, +104 ... +140 °F)
          ​0 ... 90 %RH ±5 %RH
          ​90 ... 100 %RH ±7 %RH
    Humidity sensor Vaisala INTERCAP®
    Stability ±2 %RH / 2 years
    Response time at 20 °C (+68 °F), 90 % response 15 s

    Temperature

    Measurement range
    Output scale
    Accuracy

    0 ... +40 °C (+32 ... +104 °F)
    -20 ... 0 °C, +40 ... +60 °C
    (-4 ... +32 °F, +104 ... +140 °F)Sensor


    -20 ... +60 °C (-4 ... +140 °F)
    -40 ... +60 °C (-40 ... +140 °F)

    ±0.4 °C (±0.72 °F)

    ±0.6 °C (±1.1 °F)
    Pt1000 IEC 751 Class B

    General - HMD42

    Supply voltage ​10 ... 35 VDC (RL = 0 ohm)
    ​20 ... 35 VDC (RL = 500 ohm)
    Output signal 4 ... 20mA

    General - HMD53

    Supply voltage range depends on the selected output signal
    DC
    AC
    0 … 1V 10 …35V      9 … 24V
    ​0 … 5V 14 …35V  12 … 24V
    0 … 10V 19 …35V  16 … 24V
    WITH OPTIONAL CURRENT MODULE
    ​0 ... 20 mA (RL= 0 ohm) 10 …35V  11 … 24V
    ​**0 … 20 mA (RL=500 ohm) 20 … 35V 17 … 24V
    Power consumption @ 24VAC 12mA typical
    **Optional temperature scales are available on request.​

    General

    Operating temperature range
    ​   electronics -5 ... +55 °C (+23 ... +131 °F)
    ​   probe -20 ... +60 °C (-4 ... +140 °F)
    Storage temperature range -40 ... +60 °C (-40 ... +140 °F)
    Maximum flow speed 50 m/s
    Housing material
       ​probe stainless steel
    ​   electronics cast aluminium
    Housing classification IP65 (NEMA 4)
    Connections ​screw terminal 0.5 ... 1.5 mm2
    Cable thread-through bushing for 7 ... 10 mm
    (PG9) included (18941HM)
    ​Complies with EMC standard EN61326 and EN55022 ​

    Accessories

    Armoured cable gland 10528HM
    Current module (for HMD53) 18945HM

    Spare Parts

    Vaisala INTERCAP sensor, 1 piece
    15778HM
    Vaisala INTERCAP sensor, 10 pcs INTERCAPSET-10PCS
    Membrane filter DRW010525
    Sintered filter HM46670SP