      • Compact OEM module for demand-controlled ventilation and other CO2 measurement applications
      • Incorporates the Vaisala CARBOCAP® Sensor - the silicon-based NDIR sensor with unique internal referencing
      • Advanced, single-beam, dual wavelength measurement with no moving parts
      • Excellent long-term stability
      Technical Specifications
       

       Technical Specifications

       

      Performance


      ​CO2 measurement range ​0 … 2000 ppm, 0 … 5000 ppm, 0...10000 ppm

      ​Accuracy (including repeatability, non-linearity and calibration uncertainty) ​± (2 % of range + 2 % of reading)

      ​Long-term stability ​±5% of range/5 years

      ​Response time T90 ​1 min

      ​Temperature  dependence, typical ​-0.35 % of reading / °C

      ​Pressure dependence, typical ​+0.15 % of reading/ hPa

      ​Warm-up time ​1 min, 10 min for full specification

      Product lifetime

      > 10 years

      Operating environment

       

      Temperature
      Humidity
      Pressure
      Electromagnetic compatibility

      -5 ... +45 °C (23 … 113 °F)
      0 ... 85 % RH
      700 … 1200 hPa
      EN61326-1. Generic Environment

      Inputs and outputs

       

      Operating voltage
      Power consumption
      Outputs

      24 V (±20 %) AC/DC
      <2 W
      4 … 20 mA, 0 … 10 V, RS-485, 2-wire, non-isolated

      For complete specifications, please see the brochure or manual in "Documents".