Relative humidity |
|
Measurement range |
0 ... 100 %RH |
|
Accuracy including non-linearity, hysteresis, and repeatability at 0 °C ... +40 °C |
±1.7 %RH (0 ... 90 %RH)
|
|
|
±2.5 %RH (90 ... 100 %RH)
|
|
at -40 °C ... +0 °C and at +40 °C ... +80 °C Factory calibration uncertainty at +20 °C (+68 °F)
|
±3.0 %RH (0 ... 90 %RH) ±4.0 %RH (90 ... 100 %RH) ±1.5 %RH
|
|
Humidity sensor |
Vaisala HUMICAP® 180R |
| |
Stability |
±2 %RH over 2 years |
Temperature |
|
Measurement range |
-40 ... +80 °C |
|
Accuracy over temperature range at +15 °C ... +25 °C at 0 ... +15 °C and at +25 °C ... +40°C at -40 °C ... +0 °C and at +40 °C ... +80 °C
|
±0.2 °C ±0.25 °C ±0.4 °C
|
|
Temperature Sensor
Operating temperature range transmitter body, no display transmitter body, with display HMP110 probe Storage temperature range Electromagnetic compatibility
|
Pt1000 RTD 1/3 Class B IEC 751
-40 °C ... +60 °C -20 °C ... +60 °C -40 °C ... +80 °C -50 °C ... +70 °C EN 61326-1 and EN 55022
|
Inputs and outputs
HMT120 TWO-WIRE TRANSMITTER (LOOP POWERED)
|
|
Current output signals External loop voltage
HMT130 THREE-WIRE TRANSMITTER Voltage output signals
Min output resistance Serial output Relay output Supply voltage
Current consumption at 24 VDC Max. additional error caused by the |
4 ... 20 mA 10 ... 30 VDC (RL= 0 ohms) 20 ... 30 VDC (RL< 500 ohms)
0 ... 1 V, 0 ... 5 V, 0 ... 10 V or user defined between 0 ... 10 V 1 kohm RS485, non-isolated 1 relay (max. 50 VDC, 200 mA) 10 ... 35 VDC 15 ... 35 VDC (when output 0 ... 10 V) 24 VAC (±20 %) 8 mA, if relay closed 15 mA ±0.1 % of FS output signal
|
analog outputs after calibration at +20 °C ambient temperature
|
|
Temperature dependence of the
|
±0.005 % of FS output signal
|
analog outputs
|
|
Mechanics
Materials
|
|
|
transmitter housing display window
|
PBT plastic PC plastic
|
|
probe body
|
Stainless steel (AISI 316)
|
|
probe grid filter
|
Chrome coated ABS plastic
|
|
Housing classification
|
IP65
|
|
Connections
|
|
|
inputs and outputs
|
Screw terminals 0.5 ... 1.5 mm2
|
|
probe interface
Probe cable length Display (optional)
Weight (including probe)
|
4-pin M8 female panel connector 3 m, 5 m, 10 m - up to 50 m 128 x 64 resolution full graphics B&W display without backlight 270 g
|
Accessories
|
|
Humidity and temperature probe Humidity and temperature replacement probe Constant output probe Humidity sensor Probe mounting flange Probe mounting clamps, 10 pcs
|
HMP110* HMP110R* HMP110REF* HUMICAP® 180R 226061 226067
|
HMP110 sensor protection
|
|
plastic grid filter
|
DRW010522SP
|
|
plastic grid with membrane filter stainless steel sintered filter
|
DRW010525 HM46670SP |
|
Probe cable 3 m |
HMT120Z300
|
|
Probe cable 5 m |
HMT120Z500 |
|
Probe cable 10 m Radiation shield Rain shield with installation kit Duct installation kit HMI41 connection cable HM70 connection cable USB serial interface cable
|
HMT120Z1000 DTR504A 215109 215619 25917ZZ 211339 219685 |