Performance |
|
CO2 measurement range Temperature measurement range |
0 … 2000 ppm 0 … +50°C |
|
Accuracy (including repeatability, non-linearity and calibration uncertainty)
|
± (2 % of range + 2 % of reading) |
|
Long-term stability |
±5% of range/5 years |
|
Response time T90 |
1 min |
|
Temperature dependence |
compensated |
|
Pressure dependence, typical |
+0.15 % of reading/ hPa |
|
Warm-up time |
1 min, 10 min for full specification |
|
Product lifetime |
> 10 years |
Operating environment |
|
Temperature Humidity Pressure Electromagnetic compatibility |
0 … +50°C 0 ... 85 % RH 700 … 1200 hPa Complies with EMS standard EN61326-1, Generic Environment |
Inputs and outputs |
|
Operating voltage Power consumption Outputs |
24 V (±20 %) AC/DC <2 W 0 … 10 V |